Vanguard DigiTMR User Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 86
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
REV 3 DIGITMR USER’S MANUAL
30
3.6 Performing Diagnostic Tests
3.6.1. Performing a Slow-Close Test
The DigiTMR offers a unique feature called a “Slow-Close” test. This test can measure the
distance of a breaker’s contact travel from the fully open position to the contact “touch”
position and contact wipe, or penetration distance. The test requires the operator to manually
jack the breaker’s contact from the fully open position to the fully closed position.
Contact channels 1, 2, and 3 and the transducer channel 1 are used for the “Slow-Close” test.
The DigiTMR measures the contact touch and contact wipe for each contact channel. Contact
touch is the distance measured from the contact fully open to the first position where the
contact channel is electrically closed. Contact wipe, or penetration, is the distance measured
from the contact position first electrically closed to the final closed, latching position.
To perform a “Slow-Close” test:
a. Start from the “START-UP” menu:
Press the [4] key (DIAGNOSTICS).
b. The following screen will be displayed:
Press the [1] key (SLOW CLOSE TEST).
c. The following screen will be displayed:
Press the
[ENTER] key.
d. The following screen will be displayed:
Manually close the breaker. As each contact is closed, the screen will be updated as
shown:
CONTACT 1: OPEN
CONTACT 2: OPEN
CONTACT 3: OPEN
LIFT TO CLS BRKR NOW
BRKR SLOW CLOSE TEST
RMV CB GND (1 SIDE)
“ENTER” TO BEGIN
1. SLOW CLOSE TEST
2. CHECK HOOKUP
3. TEST TRANSDUCER
4. NEXT PAGE
1. TIME BRKR 05/27/09
2. GET RSLT 10:49:23
3. SET-UP
4. DIAGNOSTICS